Stair dimensions: standard rise and run, width and headroom in US homes
ApaPlan team · Published
In a US home the standard stair rise and run under the International Residential Code (IRC R311.7) is a riser of at most 7¾ in (19.7 cm) and a tread of at least 10 in (25.4 cm), with a clear width of at least 36 in (91 cm) and headroom of at least 6 ft 8 in (203 cm). Below are all the numbers in inches and centimeters, how to work out the number of steps for your floor height, how much floor space the stair takes, and how to check it on a plan before anyone cuts a stringer.
The short answer: US residential stair dimensions
| What | Inches | Centimeters | IRC section |
|---|---|---|---|
| Riser height (maximum) | 7¾ in | 19.7 cm | R311.7.5.1 |
| Tread depth (minimum) | 10 in | 25.4 cm | R311.7.5.2 |
| Difference between the biggest and smallest riser (or tread) in one flight | ⅜ in | about 1 cm | R311.7.5.1, R311.7.5.2 |
| Clear stair width (minimum, above the handrail) | 36 in | 91 cm | R311.7.1 |
| Headroom (minimum) | 6 ft 8 in | 203 cm | R311.7.2 |
| Maximum height of one flight between floors or landings | 12 ft 7 in | 3.84 m | R311.7.3 |
| Landing depth on a straight run (minimum), and as wide as the stair | 36 in | 91 cm | R311.7.6 |
| Handrail height, measured from the line of the nosings | 34 to 38 in | 86 to 97 cm | R311.7.8.1 |
This is the US building code for one- and two-family homes, not a universal rule. Your state, county or city may adopt a different edition or change the numbers, other countries (the EU, the UK, Canada, Australia and so on) use their own, and this article is general information, not legal or engineering advice. The authority that decides is your local building department.
The IRC is published by the International Code Council (ICC). We compared its text with the Minnesota Department of Labor and Industry Code Administration Manual (March 2024) and with the residential stair guides of the Boulder County and Larimer County building departments in Colorado; the numbers above agree in all of them. The 2024 edition of the IRC renumbered the stair section to R318.7 but kept the same figures.
Rise and run: what is measured and where
- Riser height is the vertical distance between the leading edges (nosings) of two neighboring treads, not the height of the board you see. The code limit is 7¾ in (196 mm, about 19.7 cm).
- Tread depth is measured horizontally from the front edge of one tread to the front edge of the next, at a right angle to the edge. The minimum is 10 in (25.4 cm). A nosing projection of ¾ to 1¼ in (1.9 to 3.2 cm) is required unless the tread is at least 11 in (27.9 cm) deep.
- Total rise is the vertical distance from one finished floor to the next one, including the floor structure. Measure it on site, not from the ceiling height.
- Total run is the horizontal length of the stair. A flight with N risers has N − 1 treads, because the top riser ends at the floor above, so run = (N − 1) × tread depth.
Carpet, rugs and runners are not counted: the dimensions are taken on the structure, and every riser and every tread in one flight must stay within ⅜ in (9.5 mm) of the others. That uniformity matters more than it looks: people trip on one odd step.
How to calculate the number of steps
- Measure the total rise from finished floor to finished floor, for example 108 in (274 cm).
- Divide by 7¾ in and round up: 108 ÷ 7.75 = 13.9, so you need 14 risers.
- Divide the rise by the number of risers to get the real riser: 108 ÷ 14 = 7.71 in (19.6 cm).
- Multiply the treads (risers minus one) by the tread depth: 13 × 10 in = 130 in = 10 ft 10 in (330 cm) of run.
| Floor to floor | Risers | Riser height | Treads at 10 in | Total run |
|---|---|---|---|---|
| 8 ft (96 in, 244 cm) | 13 | 7.38 in (18.8 cm) | 12 | 10 ft (305 cm) |
| 9 ft (108 in, 274 cm) | 14 | 7.71 in (19.6 cm) | 13 | 10 ft 10 in (330 cm) |
| 10 ft (120 in, 305 cm) | 16 | 7.50 in (19.1 cm) | 15 | 12 ft 6 in (381 cm) |
| 11 ft (132 in, 335 cm) | 18 | 7.33 in (18.6 cm) | 17 | 14 ft 2 in (432 cm) |
These are the smallest allowed treads and the steepest allowed stair: the run in the table is a minimum, and the floor opening above has to be long enough to keep the headroom. A deeper tread, say 11 in (27.9 cm), makes the stair more comfortable but takes more floor: 14 risers with 11 in treads need 143 in, about 11 ft 11 in (363 cm).
Width, headroom and landings
- Width. At least 36 in (91 cm) clear above the handrail. At and below the handrail the clear width may drop to 31½ in (80 cm) with a handrail on one side and 27 in (69 cm) with handrails on both sides. A handrail may project no more than 4½ in (11.4 cm) into the width on each side.
- Headroom. At least 6 ft 8 in (203 cm), measured vertically from the sloped line connecting the nosings, and from the floor of any landing. Where the treads of a flight run under the edge of the floor opening above, that edge may project up to 4¾ in (12 cm) into the headroom.
- Vertical rise of one flight. No more than 12 ft 7 in (3.84 m) between floors or landings. A taller stair needs an intermediate landing.
- Landings. There must be a floor or landing at the top and at the bottom of each stair (an interior stair may skip the top landing if the door at the top does not swing over the steps). A landing is at least as wide as the stair and at least 36 in (91 cm) deep in the direction of travel on a straight run.
Handrails and guards
- When a handrail is required: on at least one side of any flight with four or more risers.
- Height: 34 to 38 in (86 to 97 cm), measured vertically from the line of the nosings.
- Grip: a round rail 1¼ to 2 in (3.2 to 5.1 cm) in diameter, or a shape with a perimeter of 4 to 6¼ in (10 to 16 cm) that you can wrap your hand around. Keep at least 1½ in (3.8 cm) between the rail and the wall.
- Continuity: the rail runs the full flight, from above the top riser to above the lowest riser, and ends at a wall, a post or a safe end return.
- Guards on open sides: required where the drop is more than 30 in (76 cm). On the open side of a stair the guard is at least 34 in (86 cm) high measured from the nosings (36 in, 91 cm, on landings and floors). Openings in a stair guard must stop a sphere 4⅜ in (11 cm) across, and the triangle between tread, riser and bottom rail must stop a 6 in (15 cm) sphere.
Winders, spiral stairs and outdoor steps
- Winder (turning) treads: at least 10 in (25.4 cm) deep at the walkline, which is 12 in (30.5 cm) from the narrow inside of the turn, and at least 6 in (15 cm) deep at any point.
- Spiral stairs: clear width at least 26 in (66 cm), tread at least 6¾ in (17 cm) deep at the walkline, riser up to 9½ in (24 cm) and headroom of 6 ft 6 in (198 cm).
- Outdoor steps. The same section covers stairs that serve a porch or deck. It does not cover stairs that are not within or serving a building, stairs to a non-habitable attic or stairs to a crawl space.
Spiral and winder stairs have their own conditions in the same section, so ask your building department before you rely on one.
Local rules can be different
The IRC is a model code: each state decides which edition to adopt and what to change. A real example is the riser and tread. Pennsylvania and Connecticut publish their residential codes with a maximum riser of 8¼ in (21 cm) and a minimum tread of 9 in (22.9 cm), while the unamended IRC, Minnesota and the two Colorado counties we checked keep 7¾ in and 10 in. Cities and counties can add amendments of their own on top of the state code.
So treat the table at the top as the model-code baseline. Before you buy lumber, ask your building department which edition applies and whether a stair that you replace has to meet the current code. Stairs in apartment buildings, shops and other public buildings follow different rules (the International Building Code and accessibility standards), and so do stairs outside the US.
If you do not have enough room
- Turn the stair. An L-shaped or U-shaped stair with a landing folds the run into a smaller footprint. The landing must be at least as wide as the stair and 36 in (91 cm) deep.
- Do not go steeper. The 7¾ in riser and 10 in tread limits are hard stops, so you cannot save floor space by shortening the treads or adding height to the risers.
- Do not shave the stairwell. A short floor opening cuts the headroom of the first steps. Check that the opening gives 6 ft 8 in (203 cm) above the nosing line, not only above the landing.
- Consider winders. A quarter-turn with winder treads is another way to change direction, but every winder has to meet the walkline rule above.
- Leave the stair to a professional. A stair changes a structural floor and an escape route, so involve a designer, an engineer or a licensed builder.
For the space around the stair (hall, doors, furniture) see furniture clearances, and if you do not have a plan of the house yet, start with how to measure a room.
How to check a stair in ApaPlan
- Open the free editor, which needs no sign-up, and draw the rooms with real wall lengths. You can work in feet and inches.
- Mark the area the stair needs: draw a narrow room as a placeholder, as long as the total run from the table above plus a 36 in (91 cm) landing, and at least 36 in (91 cm) wide.
- Use the Measure distance tool to check that the run, the landing and the space at the top and bottom fit between the walls, and that the way to the stair is wide enough.
- Open Lot & house and use the Stairs tool for steps to a front door, a terrace or between ground levels: click the bottom, then the top, and set the two levels. The panel shows the number of steps and the riser height, and you can add railings on the left, the right or both sides.
- Read the riser against the 7¾ in (19.7 cm) limit and divide the length of the stair by the number of steps minus one to get the tread. The "Comfortable" and "Steep" label in ApaPlan uses its own thresholds (a riser up to 20 cm and a tread of at least 22 cm), which are looser than the US code, so do not take it as a code check.
- Switch to 3D or the walk mode to see how the stair sits in the space, where you would hit your head, and how it looks from the entrance.
ApaPlan does not model an interior staircase with a stairwell opening in the floor above and does not check a drawing against a building code. Use it to test the space, and let your builder or building department confirm the details.
How to do it in ApaPlan
- Measure the total rise. Measure from finished floor to finished floor, for example 108 in (274 cm).
- Find the number of risers. Divide the rise by 7¾ in and round up: 108 ÷ 7.75 = 13.9, so 14 risers of about 7.71 in (19.6 cm).
- Work out the run. Treads = risers minus one. With 10 in (25.4 cm) treads, 13 treads need 130 in (10 ft 10 in, 330 cm).
- Add width, headroom and landings. Keep 36 in (91 cm) of width, 6 ft 8 in (203 cm) of headroom and a landing at least 36 in (91 cm) deep at the top and bottom.
- Check the space in ApaPlan. Draw the rooms, use Measure distance for the run and landings, try the Stairs tool for outdoor steps and look at the result in 3D.
- Confirm with your building department. Ask which code edition applies in your area, because states and cities change these numbers.
Frequently asked questions
What is the standard rise and run for stairs?
Under the US International Residential Code the riser is at most 7¾ in (19.7 cm) and the tread at least 10 in (25.4 cm). Local codes may differ, for example 8¼ in and 9 in in Pennsylvania and Connecticut.
How many steps do I need for a 9 ft floor-to-floor height?
For a rise of 108 in (274 cm) you need 14 risers of about 7.71 in (19.6 cm). That is 13 treads, so with 10 in (25.4 cm) treads the stair runs 10 ft 10 in (330 cm) along the floor.
What is the minimum stair width in a house?
36 in (91 cm) clear above the handrail. At and below the handrail it may narrow to 31½ in (80 cm) with a rail on one side or 27 in (69 cm) with rails on both sides.
How much headroom do stairs need?
At least 6 ft 8 in (203 cm), measured vertically from the sloped line that connects the nosings and from the floor of any landing. A spiral stair needs 6 ft 6 in (198 cm).
How high should a stair handrail be?
34 to 38 in (86 to 97 cm), measured vertically from the line of the nosings. A handrail is required on at least one side of a flight with four or more risers.
Does a stair need a landing?
There must be a floor or landing at the top and bottom of each stair. A landing is at least as wide as the stair and at least 36 in (91 cm) deep on a straight run, and one flight cannot rise more than 12 ft 7 in (3.84 m).
Do these stair dimensions apply outside the US?
No. They come from the US International Residential Code. The EU, the UK, Canada, Australia and other countries have their own rules with different numbers, so check the local regulation.
Is this legal or engineering advice?
No. It is general information based on the model code and state and county guides. Your local building department decides what applies, and a stair that changes the structure of a house should be designed by a qualified professional.
Can I plan a stair in ApaPlan?
Yes, for checking space. Draw the rooms, measure the run and the landing with Measure distance, use the Stairs tool in Lot & house for outdoor steps and review the result in 3D. The editor is free and needs no sign-up. It does not check a plan against a building code.